Equipotential Bonding Bar (EBB) Type 3

  • Theatre Earth Reference Bar (ERB) enclose assembly
  • 400W x 300H x 77.5D mm

Type 3 Equipotential Bonding Busbar (EBB) is designed for medical locations where patients undergo treatment or procedures, making it particularly suited to operating theatre environments. Associated anaesthetic rooms can also be bonded through the same EBB, helping provide a clear and organised approach to supplementary protective bonding across the clinical area.

The Type 3 EBB provides an accessible connection point for protective earthing conductors and supplementary equipotential bonding, while supporting straightforward inspection, testing and fault finding.

Type 3 EBB is arranged to enable single conductor connection, helping simplify installation, fault finding and ongoing inspection and testing. Clear labelling and accessible connection points support engineers throughout the installation lifecycle.

Specify on NBS

Questions? Contact us!

Equipotential Bonding Bar Type 3
Equipotential Bonding Bar Type 3
  • Theatre Earth Reference Bar (ERB) enclose assembly
  • 400W x 300H x 77.5D mm

Type 3 Equipotential Bonding Busbar (EBB) is designed for medical locations where patients undergo treatment or procedures, making it particularly suited to operating theatre environments. Associated anaesthetic rooms can also be bonded through the same EBB, helping provide a clear and organised approach to supplementary protective bonding across the clinical area.

The Type 3 EBB provides an accessible connection point for protective earthing conductors and supplementary equipotential bonding, while supporting straightforward inspection, testing and fault finding.

Type 3 EBB is arranged to enable single conductor connection, helping simplify installation, fault finding and ongoing inspection and testing. Clear labelling and accessible connection points support engineers throughout the installation lifecycle.

Specify on NBS

Questions? Contact us!

Features

  • Designed for operating theatres and rooms where patients undergo treatment or procedures
  • Associated anaesthetic rooms can be bonded through the same EBB
  • Suitable for Group 1 and Group 2 medical locations
  • 200 A copper busbar
  • 20 × 5 mm main copper bar
  • 12 × 4 mm sub copper bar
  • Available in flush or surface-mounted versions
  • 400 × 300 × 77.5 mm mild-steel enclosure
  • White powder-coated finish
  • 8 Nm connection torque setting
  • Standard and custom variants available
Person sat at their desk on the computer answering queries

Do you have any questions?

We will be happy to help you.

Contact form